Page 3: Wiring Diagrams IMPORTANT Direction of rotation is based on viewing actuator from top. To operate multiple actuators in parallel from a single source requires isolating relays in the field wiring.
4. Remove the cover bolts located around the actuator motor and control cover flange. 5. Terminate field wiring per the appropriate RCS wiring diagram, supplied with the actuator. Use a minimum of #18 AWG stranded wire. Note: Ensure the driven device is properly positioned in its full fail position. If
View and Download Dresser RCS Sure 24 installation manual online. RCS Sure 24 controller pdf manual download. Also for: Rcs sure 25.
Of Actuator .375 3.12 #10-24.50 Deep 4 Places .750. 1.500 Sq. 6.25 .436/.432 Across Flats .562/.561 (Output Shaft) Technical Data Parts List...
Problem 1: Actuator is receiving electric power but the motor does not respond. Instructions: 1a. Check actuator nameplate to insure correct model, voltage type and spring return direction. 1b. Check all wiring against installation wiring diagram. 1c. Actuator with clockwise fail position: Using a volt
Duty Cycle. The percentage of time the electric motor is energized vs. the time it is at rest, in reversing duty and with the actuator running and its rated load maximum published torque. Standard Modulating Duty Rating. 12 motor starts (corrections) per minute. At the rated duty cycle for that model.
Wiring diagram is drawn with the actuator in the open position. Use #18AWG stranded wire or better, for field hook-up. Manual operation is accomplished by use of an open-end wrench on the hex stock-coupling adapter. Direction of rotation and or position can be checked by indicator located on output shaft.